Feature / Surface probe | PVC cable | Silicone cable | PFA cable | Glass fibre cable | ||
Measurement Range | -30 °C to +105 °C | -50 °C to +180 °C | -50 °C to +260 °C | -50 °C to +400 °C | ||
Cable Material | PVC | Silicone | PFA | Glass Fibre | ||
Cable color | White/black/red/green/brown…… | |||||
IP Protection Class | IP54 | IP65 | IP54 | IP20 | ||
Probe Diameter | 4 mm, 5 mm oder 6 mm | 3 mm, 4 mm, 5 mm oder 6 mm | ||||
Cable Length | 50 mm, 100 mm, 150 mm, 200 mm, 250 mm, 300 mm, 400 mm, 500 mm | |||||
Available Measuring elements | Pt100, Pt500, Pt1000, Ni1000, | |||||
Connection Type | 2-Wire, 3-Wire, 4-Wire | |||||
Fill in Your Customizable sensor order below:
Cable Material | Cable color | Cable Length | Measuring element | Connection Type |
Others |
Surface probe - Measuring element | ||
Measuring element | Perm. range °C | Accuracy / Tolerance resistance |
Pt100 | -50 °C to +400 °C | Class B dT = ±(0,30 °C + 0,005|t|)1} |
Pt100 | -50 °C to +300 °C | Class A dT = ±(0,15 °C + 0,002|t|)1} |
Pt500 | -70 °C to +500 °C | Class B dT = ±(0,30 °C + 0,005|t|)1} |
Pt1000 | -50 °C to +400 °C | Class B dT = ±(0,30 °C + 0,005|t|)1} |
Pt1000 | -50 °C to +300 °C | Class A dT = ±(0,15 °C + 0,002|t|)1} |
NTC 5 kOhm | -40 °C to +125 °C | R25 = 5 KOhm ±1 % |
NTC 10 kOhm | -40 °C to +125 °C | R25 = 10 KOhm ±1 % |
Ni1000 | -60 °C to +150 °C | -60 °C to 0 °C: dT = ±(0,4 °C + 0,028 · T) | 0 °C to +150 °C: dT = ±(0,4 °C + 0,007 · T) |